Assessment Year | 2025 |
---|---|
Principal Product | Aluminum wire |
NAICS | 331313: Alumina Refining and Primary Aluminum Production |
SIC | 3313: Electrometallurgical Products, Except Steel |
Sales Range | $50 M to 100M |
# of Employees | 46 |
Plant Area |
150,000
ft2
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $51,475 | 1,514,000 |
kWh
|
$0.034 | |
Electricity Demand | $96,576 | 4,237 |
kW-mo/yr
|
$22.79 | |
Electricity Fees | $14,335 | - |
|
- | |
Natural Gas | $119,833 | 18,565 |
MMBtu
|
$6.45 | |
Waste Disposal Costs | |||||
Water Usage | $40,665 | 757 |
Tgal
|
$53.72 | |
TOTAL YEARLY COSTS | $322,884 | ||||
RECOMMENDED SAVINGS* | $86,585 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $55,561 | $524,124 |
$24,563
722,437
kWh
|
$30,998
-
kW-mo/yr
|
- | - | |
02 | 2.2692: Use outside cold water source as a supply of cooling water | $12,753 | $43,234 |
$479
14,094
kWh
|
$1,530
-
kW-mo/yr
|
- |
$10,744
-
Tgal
|
|
03 | 2.2437: Recover waste heat from equipment | $12,850 | $39,000 | - | - |
$12,850
-
MMBtu
|
- | |
04 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $2,595 | $5,797 | - | - |
$2,595
-
MMBtu
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $463 | - |
$463
13,622
kWh
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,025 | $525 |
$1,025
30,161
kWh
|
- | - | - | |
07 | 2.7144: Install spectral reflectors / delamp | $900 | - |
$393
11,562
kWh
|
$507
-
kW-mo/yr
|
- | - | |
08 | 2.7135: Install occupancy sensors | $438 | $941 |
$438
12,874
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $86,585 | $613,621 |
$27,361
804,750
kWh
|
$33,035
-
kW-mo/yr
|
$15,445
-
MMBtu
|
$10,744
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs