Assessment Year | 2024 |
---|---|
Principal Product | Plastic Parts |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $50 M to 100M |
# of Employees | 425 |
Plant Area |
206,000
ft2
|
Annual Production | 3,650,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $281,855 | 9,784,640 |
kWh
|
$0.029 |
Electricity Demand | $408,748 | 18,882 |
kW-mo/yr
|
$21.65 |
Electricity Fees | $156,464 | - |
|
- |
Natural Gas | $84,416 | 6,207 |
MMBtu
|
$13.60 |
TOTAL YEARLY COSTS | $931,483 | |||
RECOMMENDED SAVINGS* | $179,971 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $34,496 | $23,699 | - | - | $34,496 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,908 | $5,457 |
$8,243
286,149
kWh
|
$10,665
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $184 | $342 |
$184
6,400
kWh
|
- | - | |
04 | 2.9114: Use solar heat to make electricty | $77,264 | $788,082 |
$33,000
1,145,616
kWh
|
$44,264
-
kW-mo/yr
|
- | |
05 | 2.2692: Use outside cold water source as a supply of cooling water | $41,469 | $69,175 |
$20,405
708,367
kWh
|
$21,064
-
kW-mo/yr
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,343 | - |
$3,343
116,038
kWh
|
- | - | |
07 | 2.7243: Improve air circulation with destratification fans / other methods | $4,307 | $10,000 |
$4,307
148,512
kWh
|
- | - | |
TOTAL RECOMMENDED | $179,971 | $896,755 |
$69,482
2,411,082
kWh
|
$75,993
-
kW-mo/yr
|
$34,496 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs