Assessment Year | 2022 |
---|---|
Principal Product | automotive carpet |
NAICS | 314110: Carpet and Rug Mills |
SIC | 2273: Carpets and Rugs |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
60,000
ft2
|
Annual Production | 2,106
ton
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $659,281 | 11,221,800 |
kWh
|
$0.059 | |
Electricity Demand | $373,363 | 30,806 |
kW-mo/yr
|
$12.12 | |
Electricity Fees | $98,721 | - |
|
- | |
Natural Gas | $187,381 | 20,594 |
MMBtu
|
$9.10 | |
Waste Disposal Costs | |||||
Water Usage | $44,154 | 8,205 |
Tgal
|
$5.38 | |
Water Disposal | $92,790 | 8,205 |
Tgal
|
$11.31 | |
TOTAL YEARLY COSTS | $1,455,690 | ||||
RECOMMENDED SAVINGS* | $192,700 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $38,110 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,273 | $11,544 |
$16,947
287,244
kWh
|
$5,326
-
kW-mo/yr
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $6,394 | - |
$4,851
82,574
kWh
|
$1,543
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,208 | - |
$4,208
71,314
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,235 | $1,600 |
$5,235
88,725
kWh
|
- | - | |
05 | 2.9114: Use solar heat to make electricty | $86,119 | $765,706 |
$62,040
1,051,526
kWh
|
$24,079
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,669 | $20,000 |
$5,669
96,091
kWh
|
- | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,109 | $20,000 |
$3,109
52,697
kWh
|
- | - | |
08 | 2.9112: Use solar heat to heat water | $59,693 | $150,000 | - | - |
$59,693
-
MMBtu
|
|
TOTAL RECOMMENDED | $192,700 | $968,850 |
$102,059
1,730,171
kWh
|
$30,948
-
kW-mo/yr
|
$59,693
-
MMBtu
|
||
TOTAL IMPLEMENTED | $38,110 | $13,144 |
$31,241
529,857
kWh
|
$6,869
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs