Assessment Year | 2016 |
---|---|
Principal Product | waste water |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | less than $500 k |
# of Employees | 8 |
Plant Area |
700,000
ft2
|
Annual Production | 1,606,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $104,571 | 3,023,200 |
kWh
|
$0.035 |
Electricity Demand | $102,589 | 5,487 |
kW-mo/yr
|
$18.70 |
Electricity Fees | $2,379 | - |
|
- |
TOTAL YEARLY COSTS | $209,539 | |||
RECOMMENDED SAVINGS* | $143,061 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,087 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $125,405 | $660,000 |
$40,009
1,156,320
kWh
|
$29,620
-
kW-mo/yr
|
$55,776
-
lb
|
- | - | |
02 | 2.4321: Upgrade obsolete equipment | $15,087 | $75,544 |
$758
21,900
kWh
|
$561
-
kW-mo/yr
|
- | $1,768 | $12,000 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,569 | $9,415 |
$841
24,295
kWh
|
$1,728
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $143,061 | $744,959 |
$41,608
1,202,515
kWh
|
$31,909
-
kW-mo/yr
|
$55,776
-
lb
|
$1,768 | $12,000 | ||
TOTAL IMPLEMENTED | $15,087 | $75,544 |
$758
21,900
kWh
|
$561
-
kW-mo/yr
|
- | $1,768 | $12,000 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs