| Assessment Year | 2024 |
|---|---|
| Principal Product | Biobased Fertilizers |
| NAICS | 325311: Nitrogenous Fertilizer Manufacturing |
| SIC | 2873: Nitrogenous Fertilizers |
| Sales Range | $1 M to 5M |
| # of Employees | 20 |
| Plant Area |
50,970
ft2
|
| Annual Production | 10,000
ton
|
| Production Hrs. Annual | 2,250
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $13,278 | 162,000 |
kWh
|
$0.082 |
| Electricity Demand | $4,615 | 1,056 |
kW-mo/yr
|
$4.37 |
| Electricity Fees | $2,003 | - |
|
- |
| Natural Gas | $14,714 | 1,050 |
MMBtu
|
$14.01 |
| LPG | $11,758 | 225 |
MMBtu
|
$52.33 |
| Fuel Oil #2 | $63,095 | 2,238 |
MMBtu
|
$28.20 |
| TOTAL YEARLY COSTS | $109,463 | |||
| RECOMMENDED SAVINGS* | $503,151 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,157 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $19,157 | $112,913 |
$13,284
162,000
kWh
|
$5,873
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.3192: Use fossil fuel powered generator during peak demand periods | $1,789 | $872 |
$1,328
16,200
kWh
|
$461
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $1,409 | $5,855 |
$682
8,319
kWh
|
$727
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 4.114: Add/modify equipment to improve drying process | $308,175 | $14,388 | - | - |
$8,175
-
MMBtu
|
- | $300,000 | - | |
| 05 | 4.211: Consider use / purchase of bulk materials where possible | $150,000 | $70,000 | - | - | - | - | - | $150,000 | |
| 06 | 2.7243: Improve air circulation with destratification fans / other methods | $12,621 | $12,380 |
$(-299.0)
(-3,650)
kWh
|
$(-184.0)
-
kW-mo/yr
|
- | $13,104 | - | - | |
| 07 | 4.424: Improve space comfort conditioning | $10,000 | $1,931 |
$(-299.0)
(-3,650)
kWh
|
$(-184.0)
-
kW-mo/yr
|
- | - | $10,483 | - | |
| TOTAL RECOMMENDED | $503,151 | $218,339 |
$14,696
179,219
kWh
|
$6,693
-
kW-mo/yr
|
$8,175
-
MMBtu
|
$13,104 | $310,483 | $150,000 | ||
| TOTAL IMPLEMENTED | $19,157 | $112,913 |
$13,284
162,000
kWh
|
$5,873
-
kW-mo/yr
|
- | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs