Assessment Year | 2023 |
---|---|
Principal Product | Brass and Aluminum Foundry |
NAICS | 331529: Other Nonferrous Metal Foundries (except Die-Casting) |
SIC | 3369: Nonferrous Foundries, Except Aluminum and Copper |
Sales Range | $10 M to 50M |
# of Employees | 145 |
Plant Area |
75,048
ft2
|
Annual Production | 104,260
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $188,845 | 3,863,370 |
kWh
|
$0.049 |
Electricity Demand | $207,537 | 12,649 |
kW-mo/yr
|
$16.41 |
Electricity Fees | $10,534 | - |
|
- |
Natural Gas | $17,683 | 1,184 |
MMBtu
|
$14.93 |
TOTAL YEARLY COSTS | $424,599 | |||
RECOMMENDED SAVINGS* | $192,353 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $90,724 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $95,368 | $289,896 |
$32,365
660,510
kWh
|
$63,003
-
kW-mo/yr
|
- | - | |
02 | 2.3191: Use demand controller or load shedder | $39,683 | $20,785 |
$18,931
386,337
kWh
|
$20,752
-
kW-mo/yr
|
- | - | |
03 | 2.6231: Utilize controls to operate equipment only when needed | $18,931 | $25,400 |
$18,931
386,337
kWh
|
- | - | - | |
04 | 2.3142: User battery storage for power quality issues | $6,261 | $20,000 |
$4,292
87,600
kWh
|
$1,969
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,458 | $356 |
$4,458
90,978
kWh
|
- | - | - | |
06 | 2.7141: Lower light fixtures in high ceiling areas | $2,957 | $3,276 |
$1,575
32,124
kWh
|
$1,382
-
kW-mo/yr
|
- | - | |
07 | 2.8117: Install sub-metering equipment | $1,589 | $4,340 | - | - |
$1,589
-
MMBtu
|
- | |
08 | 2.2623: Minimize condenser cooling water temperature | $1,317 | $5,838 |
$1,317
26,885
kWh
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $1,092 | $2,160 |
$1,092
22,292
kWh
|
- | - | - | |
10 | 4.424: Improve space comfort conditioning | $20,697 | $4,480 |
$(-3,220.0)
(-65,707)
kWh
|
$(-2,073.0)
-
kW-mo/yr
|
- | $25,990 | |
TOTAL RECOMMENDED | $192,353 | $376,531 |
$79,741
1,627,356
kWh
|
$85,033
-
kW-mo/yr
|
$1,589
-
MMBtu
|
$25,990 | ||
TOTAL IMPLEMENTED | $90,724 | $66,635 |
$43,084
879,246
kWh
|
$20,061
-
kW-mo/yr
|
$1,589
-
MMBtu
|
$25,990 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs