| Assessment Year | 2022 |
|---|---|
| Principal Product | Intraocular Lenses |
| NAICS | 339112: Surgical and Medical Instrument Manufacturing |
| SIC | 3841: Surgical and Medical Instruments and Apparatus |
| Sales Range | $100 M to 500M |
| # of Employees | 60 |
| Plant Area |
102,000
ft2
|
| Annual Production | 4,286,708
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $589,014 | 11,524,402 |
kWh
|
$0.051 | |
| Electricity Demand | $54,927 | 18,109 |
kW-mo/yr
|
$3.03 | |
| Electricity Fees | $103,998 | - |
|
- | |
| Waste Disposal Costs | |||||
| Water Usage | $142,554 | 12,033 |
Tgal
|
$11.85 | |
| Water Disposal | $162,082 | 12,033 |
Tgal
|
$13.47 | |
| TOTAL YEARLY COSTS | $1,052,575 | ||||
| RECOMMENDED SAVINGS* | $713,996 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $381,249 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3417: Use waste heat with a closed-cycle gas turbine-generator set to cogenerate electricity and heat | $308,276 | $1,243,750 |
$486,462
9,538,462
kWh
|
$47,315
-
kW-mo/yr
|
$(-115,001.0)
-
MMBtu
|
- | $(-110,500.0) | |
| 02 | 2.3191: Use demand controller or load shedder | $44,987 | $62,001 |
$41,142
806,708
kWh
|
$3,845
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,746 | $33,000 |
$13,633
267,321
kWh
|
$1,113
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.2625: Chill water to the highest temperature possible | $13,240 | - |
$13,240
259,616
kWh
|
- | - | - | - | |
| 05 | 4.662: Level one – add communication using iiot devices to existing control system to modify operations | $273,973 | - | - | - | - | $273,973 | - | |
| 06 | 4.661: Level zero – install control systems for existing equipment | $58,774 | $10,000 |
$58,774
1,152,440
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $713,996 | $1,348,751 |
$613,251
12,024,547
kWh
|
$52,273
-
kW-mo/yr
|
$(-115,001.0)
-
MMBtu
|
$273,973 | $(-110,500.0) | ||
| TOTAL IMPLEMENTED | $381,249 | $1,338,751 |
$554,477
10,872,107
kWh
|
$52,273
-
kW-mo/yr
|
$(-115,001.0)
-
MMBtu
|
- | $(-110,500.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs