Assessment Year | 2019 |
---|---|
Principal Product | Panel Doors |
NAICS | 337110: Wood Kitchen Cabinet and Countertop Manufacturing |
SIC | 2434: Wood Kitchen Cabinets |
Sales Range | $5 M to 10M |
# of Employees | 25 |
Plant Area |
318,257
ft2
|
Annual Production | 75,000
units
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $70,920 | 1,423,533 |
kWh
|
$0.050 |
Electricity Demand | $73,701 | 6,252 |
kW-mo/yr
|
$11.79 |
Electricity Fees | $27,365 | - |
|
- |
LPG | $4,304 | 105 |
MMBtu
|
$41.07 |
TOTAL YEARLY COSTS | $176,290 | |||
RECOMMENDED SAVINGS* | $50,724 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $50,724 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,744 | $52,547 |
$10,907
218,130
kWh
|
$14,837
-
kW-mo/yr
|
- | |
02 | 2.7145: Install skylights | $11,989 | $45,500 |
$11,989
239,782
kWh
|
- | - | |
03 | 2.7141: Lower light fixtures in high ceiling areas | $11,027 | $7,692 |
$4,672
93,434
kWh
|
$6,355
-
kW-mo/yr
|
- | |
04 | 2.7243: Improve air circulation with destratification fans / other methods | $1,964 | $6,180 |
$(-183.0)
(-3,661)
kWh
|
$(-249.0)
-
kW-mo/yr
|
$2,396 | |
TOTAL RECOMMENDED | $50,724 | $111,919 |
$27,385
547,685
kWh
|
$20,943
-
kW-mo/yr
|
$2,396 | ||
TOTAL IMPLEMENTED | $50,724 | $111,919 |
$27,385
547,685
kWh
|
$20,943
-
kW-mo/yr
|
$2,396 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs