| Assessment Year | 2017 |
|---|---|
| Principal Product | Brass and Aluminum Alloys |
| NAICS | 331524: Aluminum Foundries (except Die-Casting) |
| SIC | 3369: Nonferrous Foundries, Except Aluminum and Copper |
| Sales Range | $10 M to 50M |
| # of Employees | 145 |
| Plant Area |
75,048
ft2
|
| Annual Production | 10,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $292,521 | 5,155,825 |
kWh
|
$0.057 | |
| Electricity Demand | $145,104 | 13,392 |
kW-mo/yr
|
$10.84 | |
| Natural Gas | $50,833 | 13,903 |
MMBtu
|
$3.66 | |
| LPG | $5,804 | 220 |
MMBtu
|
$26.38 | |
| Waste Disposal Costs | |||||
| Water Usage | $6,730 | 1,457 |
Tgal
|
$4.62 | |
| Water Disposal | $9,727 | 1,445 |
Tgal
|
$6.73 | |
| TOTAL YEARLY COSTS | $510,719 | ||||
| RECOMMENDED SAVINGS* | $74,820 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $74,820 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Water Usage Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $26,071 | $44,637 |
$15,264
269,211
kWh
|
$10,807
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $12,114 | $20,000 | - | - |
$10,874
-
MMBtu
|
$1,240
-
MMBtu
|
- | - | |
| 03 | 2.7243: Improve air circulation with destratification fans / other methods | $11,931 | $12,400 |
$8,725
153,878
kWh
|
$3,206
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,193 | $2,737 |
$4,529
79,872
kWh
|
$1,664
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,144 | $1,169 |
$6,144
107,827
kWh
|
- | - | - | - | - | |
| 06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,564 | - |
$2,204
38,865
kWh
|
$1,360
-
kW-mo/yr
|
- | - | - | - | |
| 07 | 2.7311: Ventilation system to shut off when room is not in use | $3,384 | $640 |
$2,474
43,641
kWh
|
$910
-
kW-mo/yr
|
- | - | - | - | |
| 08 | 2.7135: Install occupancy sensors | $1,548 | $478 |
$1,548
27,294
kWh
|
- | - | - | - | - | |
| 09 | 3.4154: Eliminate leaks in water lines and valves | $3,871 | $700 | - | - | - | - |
$1,566
-
Tgal
|
$2,305
-
Tgal
|
|
| TOTAL RECOMMENDED | $74,820 | $82,761 |
$40,888
720,588
kWh
|
$17,947
-
kW-mo/yr
|
$10,874
-
MMBtu
|
$1,240
-
MMBtu
|
$1,566
-
Tgal
|
$2,305
-
Tgal
|
||
| TOTAL IMPLEMENTED | $74,820 | $82,761 |
$40,888
720,588
kWh
|
$17,947
-
kW-mo/yr
|
$10,874
-
MMBtu
|
$1,240
-
MMBtu
|
$1,566
-
Tgal
|
$2,305
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Water Usage Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs