Assessment Year 2004
Principal Product Electrical Connectors
NAICS 335931: Current-Carrying Wiring Device Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range n/a
# of Employees 225
Plant Area 278,000
ft2
Annual Production 0
pieces
Production Hrs. Annual 6,240
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $373,004 4,399,823
kWh
Electricity Demand $123,916 16,615
kW-mo/yr
Natural Gas $14,680 11,162
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $105,588 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings Primary Product Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $12,849 $2,250 $12,849
225,416
kWh
- - -
02 2.4133: Use most efficient type of electric motors $13,502 $15,442 $9,295
163,070
kWh
$4,207
-
kW-mo/yr
- -
03 2.7121: Utilize daylight whenever possible in lieu of artificial light $3,562 - $2,029
35,601
kWh
$1,533
-
kW-mo/yr
- -
04 2.4239: Eliminate or reduce compressed air usage $1,546 $1,000 $1,546
27,116
kWh
- - -
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,832 - $1,832
32,135
kWh
- - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $813 $1,400 $689
12,089
kWh
$124
-
kW-mo/yr
- -
07 2.7132: Install timers on light switches in little used areas $6,509 $2,200 $1,496
26,252
kWh
$5,013
-
kW-mo/yr
- -
08 2.4239: Eliminate or reduce compressed air usage $1,009 - $1,009
17,700
kWh
- - -
09 2.7142: Utilize higher efficiency lamps and/or ballasts $1,302 $1,278 $854
14,977
kWh
$448
-
kW-mo/yr
- -
10 4.424: Improve space comfort conditioning $40,000 $5,000 - - - $40,000
11 4.311: Schedule deliveries according to demand $21,450 - - - - $21,450
12 3.5318: Recycle fluorescent lamps $1,214 $3,496 - - $1,214
-
Tgal
-
TOTAL RECOMMENDED $105,588 $32,066 $31,599
554,356
kWh
$11,325
-
kW-mo/yr
$1,214
-
Tgal
$61,450
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings Primary Product Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs