| Assessment Year | 2003 |
|---|---|
| Principal Product | Newspapers |
| NAICS | 511110: Newspaper Publishers |
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $5 M to 10M |
| # of Employees | 92 |
| Plant Area |
73,000
ft2
|
| Annual Production | 29,000,000
pieces
|
| Production Hrs. Annual | 2,496
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $340,853 | 4,090,240 |
kWh
|
$0.083 |
| Electricity Demand | $49,779 | 14,076 |
kW-mo/yr
|
$3.54 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,393 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,256 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,085 | $353 |
$1,103
16,708
kWh
|
- | $(-18.0) | - | |
| 02 | 2.4133: Use most efficient type of electric motors | $1,831 | $4,121 |
$1,580
29,267
kWh
|
$251
-
kW-mo/yr
|
- | - | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $903 | $3,000 |
$903
13,680
kWh
|
- | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,378 | - |
$1,378
20,885
kWh
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,039 | $1,906 |
$903
16,726
kWh
|
$136
-
kW-mo/yr
|
- | - | |
| 06 | 2.7135: Install occupancy sensors | $3,905 | $1,281 |
$3,905
59,167
kWh
|
- | - | - | |
| 07 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $14,685 | $20,500 |
$14,685
222,496
kWh
|
- | - | - | |
| 08 | 2.7221: Lower temperature during the winter season and vice-versa | $2,301 | $260 |
$1,609
114,100
kWh
|
$692
-
kW-mo/yr
|
- | - | |
| 09 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $1,266 | $1,895 | - | - | - | $1,266 | |
| TOTAL RECOMMENDED | $28,393 | $33,316 |
$26,066
493,029
kWh
|
$1,079
-
kW-mo/yr
|
$(-18.0) | $1,266 | ||
| TOTAL IMPLEMENTED | $6,256 | $6,640 |
$5,195
176,801
kWh
|
$1,079
-
kW-mo/yr
|
$(-18.0) | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs