Assessment Year 2002
Principal Product Grapefruit Concentrate
NAICS
n/a
SIC 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies
Sales Range $100
M
to 500
M
# of Employees 140
Plant Area 100,341
ft2
Annual Production 3,400,000
Tgal
Production Hrs. Annual 5,248
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $654,635 10,238,618
kWh
Electricity Demand $193,588 22,530
kW-mo/yr
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $348,646 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $144,422

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings Primary Product Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $3,988 $5,732 $3,089
48,264
kWh
$899
-
kW-mo/yr
- - - -
02 2.7132: Install timers on light switches in little used areas $5,901 $1,000 $5,901
71,092
kWh
- - - - -
03 2.7134: Use photocell controls $13,442 $36,067 $7,555
118,054
kWh
$6,191
-
kW-mo/yr
- $(-304.0) - -
04 2.7491: Insulate glazing, walls, ceilings, and roofs $65,908 $37,050 $65,908
794,074
kWh
- - - - -
05 2.4231: Reduce the pressure of compressed air to the minimum required $3,494 - $3,494
42,099
kWh
- - - - -
06 2.4133: Use most efficient type of electric motors $45,724 $81,293 $32,324
505,056
kWh
$13,400
-
kW-mo/yr
- - - -
07 2.2437: Recover waste heat from equipment $27,545 $120,962 - - $27,791
-
MMBtu
$(-246.0) - -
08 2.6218: Turn off equipment when not in use $20,543 - $15,719
245,604
kWh
$4,824
-
kW-mo/yr
- - - -
09 2.7124: Make a practice of turning off lights when not needed $3,134 - $2,101
32,826
kWh
$1,033
-
kW-mo/yr
- - - -
10 3.6193: Install equipment (eg compactor) to reduce disposal costs $30,592 $15,000 - - - - $30,592 -
11 3.5318: Recycle fluorescent lamps $63 - - - - - $63 -
12 4.441: Install automatic packing equipment $126,744 $400,000 - - - - - $126,744
13 4.652: Replace existing equipment with more suitable substitutes $1,568 $1,487 - - - - $1,568 -
TOTAL RECOMMENDED $348,646 $698,591 $136,091
1,857,069
kWh
$26,347
-
kW-mo/yr
$27,791
-
MMBtu
$(-550.0) $32,223 $126,744
TOTAL IMPLEMENTED $144,422 $125,562 $122,635
1,667,923
kWh
$20,156
-
kW-mo/yr
- - $1,631 -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings One-time Revenue or Avoided Cost Savings Primary Product Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs