| Assessment Year | 2000 |
|---|---|
| Principal Product | Plastic Foam Products |
| NAICS |
n/a
|
| SIC | 3086: Plastics Foam Products |
| Sales Range | $10 M to 50M |
| # of Employees | 97 |
| Plant Area |
120,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $138,403 | 3,325,616 |
kWh
|
$0.042 |
| Electricity Demand | $88,358 | 9,223 |
kW-mo/yr
|
$9.58 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $75,601 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $42,866 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,084 | $2,894 |
$3,582
85,287
kWh
|
$1,502
-
kW-mo/yr
|
- | |
| 02 | 2.8121: Apply for tax-free status for energy purchases | $10,589 | $50 | - | - | $10,589 | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,167 | $840 |
$217
5,275
kWh
|
$68
-
kW-mo/yr
|
$882 | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,364 | $470 |
$1,418
20,809
kWh
|
- | $(-54.0) | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,026 | - |
$2,026
29,894
kWh
|
- | - | |
| 06 | 2.7141: Lower light fixtures in high ceiling areas | $7,811 | $28,082 |
$8,086
192,556
kWh
|
- | $(-275.0) | |
| 07 | 2.4238: Do not use compressed air for personal cooling | $1,365 | $1,212 |
$1,365
20,223
kWh
|
- | - | |
| 08 | 2.4133: Use most efficient type of electric motors | $19,701 | $12,130 |
$14,341
199,004
kWh
|
$5,360
-
kW-mo/yr
|
- | |
| 09 | 3.4155: Meter waste water | $1,570 | $1,500 | - | - | $1,570 | |
| 10 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $9,324 | - | - | - | $9,324 | |
| 11 | 4.125: | $15,600 | $1,100 | - | - | $15,600 | |
| TOTAL RECOMMENDED | $75,601 | $48,278 |
$31,035
553,048
kWh
|
$6,930
-
kW-mo/yr
|
$37,636 | ||
| TOTAL IMPLEMENTED | $42,866 | $19,096 |
$22,949
360,492
kWh
|
$6,930
-
kW-mo/yr
|
$12,987 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs