Assessment Year | 2000 |
---|---|
Principal Product | Chocolate Candies |
NAICS |
n/a
|
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | n/a |
# of Employees | 77 |
Plant Area |
n/a
|
Annual Production | 12,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $139,756 | 3,599,062 |
kWh
|
$0.039 |
Electricity Demand | $75,336 | 9,527 |
kW-mo/yr
|
$7.91 |
LPG | $3,063 | 384 |
MMBtu
|
$7.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,380 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,901 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,479 | $7,893 |
$1,511
35,170
kWh
|
$968
-
kW-mo/yr
|
- | - | - | |
02 | 2.2515: Use optimum thickness insulation | $1,894 | $1,361 |
$1,894
43,962
kWh
|
- | - | - | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $1,287 | - |
$1,103
8,792
kWh
|
$184
-
kW-mo/yr
|
- | - | - | |
04 | 2.2223: Enhance sensitivity of temperature control and cutoff | $584 | $20 | - | - |
$584
-
MMBtu
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,670 | - |
$3,670
58,324
kWh
|
- | - | - | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $6,767 | $1,605 | - |
$(-223.0)
-
kW-mo/yr
|
- | - | $6,990 | |
07 | 4.652: Replace existing equipment with more suitable substitutes | $1,699 | $2,720 |
$917
7,913
kWh
|
$442
-
kW-mo/yr
|
- | $340 | - | |
TOTAL RECOMMENDED | $18,380 | $13,599 |
$9,095
154,161
kWh
|
$1,371
-
kW-mo/yr
|
$584
-
MMBtu
|
$340 | $6,990 | ||
TOTAL IMPLEMENTED | $15,901 | $5,706 |
$7,584
118,991
kWh
|
$403
-
kW-mo/yr
|
$584
-
MMBtu
|
$340 | $6,990 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Administrative Changes Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs