| Assessment Year | 1997 |
|---|---|
| Principal Product | Newspapers |
| NAICS |
n/a
|
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $5 M to 10M |
| # of Employees | 284 |
| Plant Area |
67,000
ft2
|
| Annual Production | 17,190,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $177,176 | 3,603,165 |
kWh
|
$0.049 |
| Electricity Demand | $66,385 | 6,997 |
kW-mo/yr
|
$9.49 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $101,395 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $6,071 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,094 | $45,707 |
$18,883
385,404
kWh
|
$3,211
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,253 | $1,352 |
$6,279
128,077
kWh
|
$974
-
kW-mo/yr
|
- | |
| 03 | 2.7132: Install timers on light switches in little used areas | $7,567 | $1,800 |
$7,567
154,455
kWh
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $10,982 | $1,856 |
$10,982
224,209
kWh
|
- | - | |
| 05 | 2.2515: Use optimum thickness insulation | $7,093 | $3,500 |
$7,093
104,338
kWh
|
- | - | |
| 06 | 2.3113: Make ice during off peak hours for cooling | $27,537 | $59,500 | - |
$27,537
-
kW-mo/yr
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,664 | $1,100 |
$3,664
53,927
kWh
|
- | - | |
| 08 | 2.4133: Use most efficient type of electric motors | $291 | $405 |
$212
4,396
kWh
|
$79
-
kW-mo/yr
|
- | |
| 09 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $5,235 | $11,000 | - | - | $5,235 | |
| 10 | 3.5316: Contract a wood pallet recycling company | $2,407 | - | - | - | $2,407 | |
| 11 | 4.126: Install sensors to detect defects | $7,272 | $2,400 | - | - | $7,272 | |
| TOTAL RECOMMENDED | $101,395 | $128,620 |
$54,680
1,054,806
kWh
|
$31,801
-
kW-mo/yr
|
$14,914 | ||
| TOTAL IMPLEMENTED | $6,071 | $1,100 |
$3,664
53,927
kWh
|
- | $2,407 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs