| Assessment Year | 1997 |
|---|---|
| Principal Product | PVC Pipe |
| NAICS |
n/a
|
| SIC | 3084: Plastics Pipe |
| Sales Range | $5 M to 10M |
| # of Employees | 28 |
| Plant Area |
34,000
ft2
|
| Annual Production | 25,000,000
lb
|
| Production Hrs. Annual | 8,640
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $270,191 | 5,097,890 |
kWh
|
$0.053 |
| Electricity Demand | $17,376 | 9,505 |
kW-mo/yr
|
$1.83 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $37,597 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $34,450 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | By-product Production Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,676 | $18,899 |
$6,333
119,578
kWh
|
$343
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4133: Use most efficient type of electric motors | $954 | $5,432 |
$908
16,999
kWh
|
$46
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,538 | $2,350 |
$11,538
202,521
kWh
|
- | - | - | - | |
| 04 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $3,147 | $2,000 | - | - |
$2,400
-
lb
|
- | $747 | |
| 05 | 4.431: Train operators for maximum operating efficiency | $15,282 | - | - | - | - | $15,282 | - | |
| TOTAL RECOMMENDED | $37,597 | $28,681 |
$18,779
339,098
kWh
|
$389
-
kW-mo/yr
|
$2,400
-
lb
|
$15,282 | $747 | ||
| TOTAL IMPLEMENTED | $34,450 | $26,681 |
$18,779
339,098
kWh
|
$389
-
kW-mo/yr
|
- | $15,282 | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs