| Assessment Year | 1996 |
|---|---|
| Principal Product | Corrugated Materials |
| NAICS |
n/a
|
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $10 M to 50M |
| # of Employees | 87 |
| Plant Area |
300,000
ft2
|
| Annual Production | 720,000
thousand feet
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $249,830 | 5,439,625 |
kWh
|
$0.046 |
| Electricity Demand | $126,987 | 15,176 |
kW-mo/yr
|
$8.37 |
| Natural Gas | $145,737 | 57,935 |
MMBtu
|
$2.52 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $46,641 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $32,838 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,138 | $11,595 |
$2,712
59,203
kWh
|
$1,426
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,663 | $3,726 |
$1,739
37,808
kWh
|
$924
-
kW-mo/yr
|
- | - | |
| 03 | 2.7145: Install skylights | $2,135 | $2,560 |
$2,135
52,169
kWh
|
- | - | - | |
| 04 | 2.7132: Install timers on light switches in little used areas | $3,155 | $2,220 |
$3,155
68,875
kWh
|
- | - | - | |
| 05 | 2.4133: Use most efficient type of electric motors | $4,007 | $13,149 |
$2,622
57,151
kWh
|
$1,385
-
kW-mo/yr
|
- | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,222 | $850 |
$4,222
60,961
kWh
|
- | - | - | |
| 07 | 2.2136: Install / repair insulation on steam lines | $1,712 | $5,490 | - | - |
$1,712
-
MMBtu
|
- | |
| 08 | 3.4111: Use closed cycle process to minimize waste water production | $22,535 | $24,000 | - | - | - |
$22,535
-
Tgal
|
|
| 09 | 3.4116: Meter recycled water (to reduce sewer charges) | $2,074 | $2,000 | - | - | - |
$2,074
-
Tgal
|
|
| TOTAL RECOMMENDED | $46,641 | $65,590 |
$16,585
336,167
kWh
|
$3,735
-
kW-mo/yr
|
$1,712
-
MMBtu
|
$24,609
-
Tgal
|
||
| TOTAL IMPLEMENTED | $32,838 | $39,999 |
$6,844
118,112
kWh
|
$1,385
-
kW-mo/yr
|
- |
$24,609
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs