ITAC Assessment: UF0154
ITAC logo
ITAC Assessment: UF0154
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1996
Principal Product Bottled Rum
NAICS
n/a
SIC 2085: Distilled and Blended Liquors
Sales Range $50
M
to 100
M
# of Employees 265
Plant Area 450,000
ft2
Annual Production 5,000,000
units
Production Hrs. Annual 5,200
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $244,611 6,474,209
kWh
Electricity Demand $131,367 15,231
kW-mo/yr
Fuel Oil #2 $39,369 5,300
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $35,971 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $26,798

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Fuel Oil #2 Savings Other Liquid (haz) Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $15,239 $34,886 $9,751
256,741
kWh
$5,488
-
kW-mo/yr
- -
02 2.4133: Use most efficient type of electric motors $830 $1,749 $501
13,189
kWh
$329
-
kW-mo/yr
- -
03 2.7111: Reduce illumination to minimum necessary levels $4,031 $4,640 $2,643
69,461
kWh
$1,388
-
kW-mo/yr
- -
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $443 - $443
11,723
kWh
- - -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,265 $1,350 $5,265
90,856
kWh
- - -
06 2.2425: Use flue gases to heat process or service water $9,173 $24,000 - - $9,173
-
MMBtu
-
07 3.1175: Use a different or recycled raw material $990 - - - - $990
-
gal
TOTAL RECOMMENDED $35,971 $66,625 $18,603
441,970
kWh
$7,205
-
kW-mo/yr
$9,173
-
MMBtu
$990
-
gal
TOTAL IMPLEMENTED $26,798 $42,625 $18,603
441,970
kWh
$7,205
-
kW-mo/yr
- $990
-
gal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Fuel Oil #2 Savings Other Liquid (haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs