Assessment Year | 1995 |
---|---|
Principal Product | Business Machinery Plastics |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
180,000
ft2
|
Annual Production | 40,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $362,714 | 5,816,530 |
kWh
|
$0.062 |
Natural Gas | $30,397 | 5,099 |
MMBtu
|
$5.96 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $59,322 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,418 | $10,501 |
$10,418
192,556
kWh
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,083 | $5,832 |
$3,083
48,359
kWh
|
|
03 | 2.4133: Use most efficient type of electric motors | $4,277 | $4,277 |
$4,277
71,219
kWh
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $23,009 | $38,849 |
$23,009
533,705
kWh
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,519 | $350 |
$2,519
40,445
kWh
|
|
06 | 2.7135: Install occupancy sensors | $1,000 | $1,200 |
$1,000
23,154
kWh
|
|
07 | 2.2443: Re-use or recycle hot or cold process exhaust air | $10,056 | $18,750 |
$10,056
233,294
kWh
|
|
08 | 2.7232: Replace existing hvac unit with high efficiency model | $4,960 | $3,650 |
$4,960
50,117
kWh
|
|
TOTAL RECOMMENDED | $59,322 | $83,409 |
$59,322
1,192,849
kWh
|
||
TOTAL IMPLEMENTED | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs