| Assessment Year | 1995 |
|---|---|
| Principal Product | Pine plywood |
| NAICS |
n/a
|
| SIC | 2435: Hardwood Veneer and Plywood |
| Sales Range | $100 M to 500M |
| # of Employees | 380 |
| Plant Area |
28,200
ft2
|
| Annual Production | 369,375
thousand feet
|
| Production Hrs. Annual | 8,520
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,156,491 | 43,490,915 |
kWh
|
$0.050 |
| LPG | $76,682 | 12,656 |
MMBtu
|
$6.06 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $1,822,097 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $71,294 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Wood Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,672 | $9,944 |
$2,672
37,222
kWh
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,683 | $18,125 |
$11,683
235,053
kWh
|
- | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $46,162 | $114,584 |
$46,162
883,646
kWh
|
- | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $74,087 | $149,527 |
$74,087
1,986,225
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $25,132 | $2,000 |
$25,132
495,604
kWh
|
- | - | |
| 06 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $1,503,626 | $4,550,000 |
$2,156,491
43,503,225
kWh
|
$(-1,366,270.0)
-
MMBtu
|
$713,405
-
MMBtu
|
|
| 07 | 2.3137: Use power during off-peak periods | $72,554 | - |
$72,554
-
kWh
|
- | - | |
| 08 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $86,181 | $84,000 | - | - |
$86,181
-
MMBtu
|
|
| TOTAL RECOMMENDED | $1,822,097 | $4,928,180 |
$2,388,781
47,140,975
kWh
|
$(-1,366,270.0)
-
MMBtu
|
$799,586
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $71,294 | $116,584 |
$71,294
1,379,250
kWh
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Wood Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs