| Assessment Year | 1994 |
|---|---|
| Principal Product | Concrete Roof Tiles |
| NAICS |
n/a
|
| SIC | 3272: Concrete Products, Except Block and Brick |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
2,178,000
ft2
|
| Annual Production | 360
thousand feet
|
| Production Hrs. Annual | 5,460
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $137,820 | 2,510,844 |
kWh
|
$0.055 |
| Other Energy | $106,625 | 22,026 |
MMBtu
|
$4.84 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $100,865 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,615 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Other Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,448 | $5,894 |
$5,448
85,287
kWh
|
- | |
| 02 | 2.7134: Use photocell controls | $116 | $200 |
$116
2,638
kWh
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $405 | $1,000 |
$405
7,327
kWh
|
- | |
| 04 | 2.4133: Use most efficient type of electric motors | $6,602 | $7,601 |
$6,602
119,578
kWh
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,762 | $2,425 |
$1,762
31,946
kWh
|
- | |
| 06 | 2.4239: Eliminate or reduce compressed air usage | $16,000 | $7,000 |
$16,000
291,032
kWh
|
- | |
| 07 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $70,532 | $52,995 | - |
$70,532
-
MMBtu
|
|
| TOTAL RECOMMENDED | $100,865 | $77,115 |
$30,333
537,808
kWh
|
$70,532
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $23,615 | $16,319 |
$23,615
415,592
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Other Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs