ITAC Assessment: UF0071
ITAC logo
ITAC Assessment: UF0071
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 1993
Principal Product Gypsum Wallboard
NAICS
n/a
SIC 3275: Gypsum Products
Sales Range $10
M
to 50
M
# of Employees 82
Plant Area 500,000
ft2
Annual Production 38,000
ton
Production Hrs. Annual 6,000
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $758,157 11,398,300
kWh
Natural Gas $1,252,538 615,017
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $697,506 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $36,794

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Administrative Changes Savings
01 2.3417: Use waste heat with a closed-cycle gas turbine-generator set to cogenerate electricity and heat $626,778 $1,320,000 - $626,778
02 2.4133: Use most efficient type of electric motors $33,681 $40,138 $33,681
502,638
kWh
-
03 2.4111: Utilize energy-efficient belts and other improved mechanisms $23,794 $15,169 $23,794
355,217
kWh
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $9,517 $1,550 $9,517
142,145
kWh
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $2,173 $1,156 $2,173
32,532
kWh
-
06 2.7135: Install occupancy sensors $306 $448 $306
5,862
kWh
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $630 $1,779 $630
9,379
kWh
-
08 2.7232: Replace existing hvac unit with high efficiency model $310 $1,150 $310
4,689
kWh
-
09 2.3212: Optimize plant power factor $317 $1,000 $317
6,155
kWh
-
TOTAL RECOMMENDED $697,506 $1,382,390 $70,728
1,058,617
kWh
$626,778
TOTAL IMPLEMENTED $36,794 $44,223 $36,794
549,238
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs