| Assessment Year | 1993 |
|---|---|
| Principal Product | Wood I-beams |
| NAICS |
n/a
|
| SIC | 2439: Structural Wood Members, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 48 |
| Plant Area |
15,000
ft2
|
| Annual Production | 5,000
thousand feet
|
| Production Hrs. Annual | 3,900
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $73,867 | 1,019,344 |
kWh
|
$0.072 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $21,842 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,265 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,372 | $350 |
$1,372
15,240
kWh
|
|
| 02 | 2.7144: Install spectral reflectors / delamp | $560 | $1,620 |
$560
4,689
kWh
|
|
| 03 | 2.3212: Optimize plant power factor | $9,259 | $15,000 |
$9,259
-
kWh
|
|
| 04 | 2.4133: Use most efficient type of electric motors | $3,682 | $6,727 |
$3,682
42,497
kWh
|
|
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,417 | $680 |
$1,417
15,826
kWh
|
|
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,758 | $6,000 |
$3,758
41,618
kWh
|
|
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,794 | $1,450 |
$1,794
19,930
kWh
|
|
| TOTAL RECOMMENDED | $21,842 | $31,827 |
$21,842
139,800
kWh
|
||
| TOTAL IMPLEMENTED | $8,265 | $9,207 |
$8,265
93,493
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs