Assessment Year | 1992 |
---|---|
Principal Product | MEN'S SLACKS |
NAICS |
n/a
|
SIC | 2325: Men's and Boys' Separate Trousers and Slacks |
Sales Range | $5 M to 10M |
# of Employees | 160 |
Plant Area |
n/a
|
Annual Production | 780,000
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $27,842 | 395,076 |
kWh
|
$0.070 |
LPG | $17,446 | 1,693 |
MMBtu
|
$10.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,828 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | LPG Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $741 | $731 |
$741
10,551
kWh
|
- | |
02 | 2.7144: Install spectral reflectors / delamp | $2,525 | $14,685 |
$2,525
36,049
kWh
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $60 | $870 |
$60
879
kWh
|
- | |
04 | 2.7233: Use properly designed and sized hvac equipment | $4,712 | $4,000 |
$4,712
67,409
kWh
|
- | |
05 | 2.7492: Use proper thickness of insulation on building envelope | $2,192 | $8,374 |
$2,192
31,360
kWh
|
- | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,928 | $669 | - |
$1,928
-
MMBtu
|
|
07 | 2.2414: Use waste heat from hot flue gases to preheat | $670 | $2,125 | - |
$670
-
MMBtu
|
|
TOTAL RECOMMENDED | $12,828 | $31,454 |
$10,230
146,248
kWh
|
$2,598
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs