| Assessment Year | 1991 |
|---|---|
| Principal Product | POTATO AND CORN CHIPS |
| NAICS |
n/a
|
| SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
| Sales Range | $10 M to 50M |
| # of Employees | 65 |
| Plant Area |
n/a
|
| Annual Production | 3,000,000
pieces
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $190,392 | 2,735,932 |
kWh
|
$0.070 |
| Natural Gas | $118,108 | 26,061 |
MMBtu
|
$4.53 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $15,919 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7144: Install spectral reflectors / delamp | $8,472 | $7,770 |
$8,472
121,043
kWh
|
- | |
| 02 | 2.4133: Use most efficient type of electric motors | $818 | $1,805 |
$818
11,723
kWh
|
- | |
| 03 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,212 | - |
$4,212
-
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,038 | - |
$1,038
14,947
kWh
|
- | |
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $928 | $600 | - |
$928
-
MMBtu
|
|
| 06 | 2.4322: Use or replace with energy efficient substitutes | $395 | $2,443 |
$395
5,569
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $56 | $291 |
$56
879
kWh
|
- | |
| TOTAL RECOMMENDED | $15,919 | $12,909 |
$14,991
154,161
kWh
|
$928
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs