| Assessment Year | 2026 |
|---|---|
| Principal Product | Complex Wax Patterns, Gauges, Fixtures, Tools, Dies |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 136 |
| Plant Area |
82,060
ft2
|
| Annual Production | 1,001
units
|
| Production Hrs. Annual | 3,640
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $287,182 | 2,511,731 |
kWh
|
$0.11 | |
| Electricity Demand | $45,155 | 5,984 |
kW-mo/yr
|
$7.55 | |
| Electricity Fees | $91 | - |
|
- | |
| Natural Gas | $15,450 | 2,126 |
MMBtu
|
$7.27 | |
| Waste Disposal Costs | |||||
| Water Usage | $996 | 161 |
Tgal
|
$6.19 | |
| TOTAL YEARLY COSTS | $348,874 | ||||
| RECOMMENDED SAVINGS* | $110,509 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6218: Turn off equipment when not in use | $19,731 | - |
$19,731
172,624
kWh
|
- | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,254 | $1,000 |
$13,072
114,362
kWh
|
$1,182
-
kW-mo/yr
|
- | - | |
| 03 | 2.4239: Eliminate or reduce compressed air usage | $5,715 | $3,500 |
$5,715
50,003
kWh
|
- | - | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $11,563 | - |
$10,604
92,772
kWh
|
$959
-
kW-mo/yr
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $32,518 | $10,472 |
$20,686
180,981
kWh
|
$4,502
-
kW-mo/yr
|
- | $7,330 | |
| 06 | 2.7122: Disconnect ballasts | $2,026 | $250 |
$1,664
14,560
kWh
|
$362
-
kW-mo/yr
|
- | - | |
| 07 | 2.7241: Install outside air damper / economizer on hvac unit | $5,912 | $2,116 |
$5,912
51,727
kWh
|
- | - | - | |
| 08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $16,089 | $15,412 |
$13,213
115,598
kWh
|
$2,876
-
kW-mo/yr
|
- | - | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,367 | $1,712 |
$1,123
9,822
kWh
|
$244
-
kW-mo/yr
|
- | - | |
| 10 | 2.3212: Optimize plant power factor | $1,334 | $5,368 | - | - | $1,334 | - | |
| TOTAL RECOMMENDED | $110,509 | $39,830 |
$91,720
802,449
kWh
|
$10,125
-
kW-mo/yr
|
$1,334 | $7,330 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs