Assessment Year | 2022 |
---|---|
Principal Product | Circuits and Cable Harnesses |
NAICS | 334412: Bare Printed Circuit Board Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
31,210
ft2
|
Annual Production | 1,705,322
units
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $48,470 | 797,316 |
kWh
|
$0.061 | |
Electricity Demand | $16,668 | 2,604 |
kW-mo/yr
|
$6.40 | |
Electricity Fees | $12,309 | - |
|
- | |
Natural Gas | $7,925 | 896 |
MMBtu
|
$8.84 | |
Waste Disposal Costs | |||||
Water Usage | $2,309 | 304 |
Tgal
|
$7.60 | |
Water Disposal | $1,640 | 304 |
Tgal
|
$5.39 | |
Solid Waste (non-haz) | $20,800 | 12,000 |
lb
|
$1.73 | |
TOTAL YEARLY COSTS | $110,121 | ||||
RECOMMENDED SAVINGS* | $35,318 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $32,357 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $12,359 | - | - | - | - | $1,959 | $10,400 | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $936 | - |
$836
5,928
kWh
|
$100
-
kW-mo/yr
|
- | - | - | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $5,243 | $400 |
$5,243
37,186
kWh
|
- | - | - | - | |
04 | 2.2511: Insulate bare equipment | $199 | $44 |
$152
1,080
kWh
|
$47
-
kW-mo/yr
|
- | - | - | |
05 | 3.4116: Meter recycled water (to reduce sewer charges) | $671 | $256 | - | - |
$671
-
Tgal
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,155 | $1,552 |
$1,002
7,109
kWh
|
$153
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,755 | $26,460 |
$12,305
87,268
kWh
|
$1,881
-
kW-mo/yr
|
- | - | $569 | |
TOTAL RECOMMENDED | $35,318 | $28,712 |
$19,538
138,571
kWh
|
$2,181
-
kW-mo/yr
|
$671
-
Tgal
|
$1,959 | $10,969 | ||
TOTAL IMPLEMENTED | $32,357 | $26,860 |
$17,548
124,454
kWh
|
$1,881
-
kW-mo/yr
|
- | $1,959 | $10,969 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs