Assessment Year | 2022 |
---|---|
Principal Product | Water |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $10 M to 50M |
# of Employees | 30 |
Plant Area |
120,000
ft2
|
Annual Production | 4,740,302
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $635,981 | 16,294,680 |
kWh
|
$0.039 | |
Electricity Demand | $268,351 | 24,792 |
kW-mo/yr
|
$10.82 | |
Electricity Fees | $31,542 | - |
|
- | |
Waste Disposal Costs | |||||
Water Disposal | $1,913 | 276 |
Tgal
|
$6.93 | |
TOTAL YEARLY COSTS | $937,787 | ||||
RECOMMENDED SAVINGS* | $32,009 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $5,844 | - |
$5,844
149,731
kWh
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,705 | $30,000 |
$6,492
171,793
kWh
|
$213
-
kW-mo/yr
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $540 | - |
$391
10,006
kWh
|
$149
-
kW-mo/yr
|
|
04 | 3.1161: Eliminate/reduce an operation | $213 | - |
$213
5,446
kWh
|
- | |
05 | 2.7234: Use heat pump for space conditioning | $18,707 | $62,108 |
$18,707
479,291
kWh
|
- | |
TOTAL RECOMMENDED | $32,009 | $92,108 |
$31,647
816,267
kWh
|
$362
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs