Assessment Year | 2022 |
---|---|
Principal Product | Metal Closures |
NAICS | 332119: Metal Crown, Closure, and Other Metal Stamping (except Automotive) |
SIC | 3466: Crowns and Closures |
Sales Range | $50 M to 100M |
# of Employees | 135 |
Plant Area |
465,000
ft2
|
Annual Production | 5,000,000,000
units
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $497,721 | 15,481,200 |
kWh
|
$0.032 |
Electricity Demand | $633,786 | 26,265 |
kW-mo/yr
|
$24.13 |
Electricity Fees | $17,554 | - |
|
- |
Natural Gas | $265,254 | 76,289 |
MMBtu
|
$3.48 |
TOTAL YEARLY COSTS | $1,414,315 | |||
RECOMMENDED SAVINGS* | $76,925 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,284 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $22,050 | - |
$6,176
192,095
kWh
|
$15,874
-
kW-mo/yr
|
- | - | - | |
02 | 2.6212: Turn off equipment during breaks, reduce operating time | $128 | - |
$128
3,979
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $29,591 | $604 |
$14,590
453,817
kWh
|
$15,001
-
kW-mo/yr
|
- | - | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $6,603 | $6,300 |
$2,134
66,366
kWh
|
$4,469
-
kW-mo/yr
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,106 | $5,256 |
$1,823
56,706
kWh
|
$5,349
-
kW-mo/yr
|
- | $548 | $386 | |
06 | 2.7224: Reduce space conditioning during non-working hours | $150 | $50 | - | - |
$150
-
MMBtu
|
- | - | |
07 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $10,297 | $12,000 | - | - |
$10,297
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $76,925 | $24,210 |
$24,851
772,963
kWh
|
$40,693
-
kW-mo/yr
|
$10,447
-
MMBtu
|
$548 | $386 | ||
TOTAL IMPLEMENTED | $30,284 | $5,256 |
$8,127
252,780
kWh
|
$21,223
-
kW-mo/yr
|
- | $548 | $386 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs