Assessment Year | 2020 |
---|---|
Principal Product | Inkjet Printing Systems and Consumables |
NAICS | 333244: Printing Machinery and Equipment Manufacturing |
SIC | 3555: Printing Trades Machinery and Equipment |
Sales Range | $100 M to 500M |
# of Employees | 299 |
Plant Area |
315,000
ft2
|
Annual Production | 533,117
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $801,378 | 17,651,504 |
kWh
|
$0.045 | |
Electricity Demand | $118,707 | 32,460 |
kW-mo/yr
|
$3.66 | |
Electricity Fees | $315,878 | - |
|
- | |
Natural Gas | $191,113 | 46,463 |
MMBtu
|
$4.11 | |
Waste Disposal Costs | |||||
Water Usage | $77,123 | 14,945 |
Tgal
|
$5.16 | |
Water Disposal | $94,106 | 14,945 |
Tgal
|
$6.30 | |
TOTAL YEARLY COSTS | $1,598,305 | ||||
RECOMMENDED SAVINGS* | $86,955 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $15,303 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,684 | - | - | - |
$2,684
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,924 | $1,000 |
$4,380
108,405
kWh
|
$544
-
kW-mo/yr
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,086 | - |
$3,635
89,974
kWh
|
$451
-
kW-mo/yr
|
- | - | - | |
04 | 3.4116: Meter recycled water (to reduce sewer charges) | $9,326 | $1,400 | - | - | - |
$9,326
-
Tgal
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $28,713 | $11,014 |
$14,027
347,199
kWh
|
- |
$14,686
-
MMBtu
|
- | - | |
06 | 2.7241: Install outside air damper / economizer on hvac unit | $21,134 | $7,500 |
$21,134
522,618
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,619 | $82,620 |
$7,991
197,803
kWh
|
$3,035
-
kW-mo/yr
|
- | - | $1,593 | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,469 | $10,920 |
$2,952
73,058
kWh
|
$732
-
kW-mo/yr
|
- | - | $(-215.0) | |
TOTAL RECOMMENDED | $86,955 | $114,454 |
$54,119
1,339,057
kWh
|
$4,762
-
kW-mo/yr
|
$17,370
-
MMBtu
|
$9,326
-
Tgal
|
$1,378 | ||
TOTAL IMPLEMENTED | $15,303 | $82,620 |
$7,991
197,803
kWh
|
$3,035
-
kW-mo/yr
|
$2,684
-
MMBtu
|
- | $1,593 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs