Assessment Year | 2017 |
---|---|
Principal Product | Ceramic actuators |
NAICS | 333314: Optical Instrument and Lens Manufacturing |
SIC | 3827: Optical Instruments and Lenses |
Sales Range | $10 M to 50M |
# of Employees | 30 |
Plant Area |
50,000
ft2
|
Annual Production | 6
units
|
Production Hrs. Annual | 2,040
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $180,639 | 2,441,120 |
kWh
|
$0.074 | |
Electricity Demand | $141,725 | 9,266 |
kW-mo/yr
|
$15.30 | |
Electricity Fees | $22,061 | - |
|
- | |
Natural Gas | $7,399 | 650 |
MMBtu
|
$11.38 | |
Waste Disposal Costs | |||||
Water Usage | $1,081 | 122,680 |
Tgal
|
$0.009 | |
TOTAL YEARLY COSTS | $352,905 | ||||
RECOMMENDED SAVINGS* | $76,542 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $20,697 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $28,320 | $16,929 | - |
$28,320
-
kW-mo/yr
|
- | - | |
02 | 2.8121: Apply for tax-free status for energy purchases | $20,697 | $100 | - | - | $20,697 | - | |
03 | 2.7229: Air condition only space necessary | $13,365 | $7,900 |
$13,365
180,614
kWh
|
- | - | - | |
04 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $10,486 | $21,000 |
$10,486
141,697
kWh
|
- | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,966 | $20,488 |
$2,966
40,080
kWh
|
- | - | - | |
06 | 2.2531: Re-size charging openings or add movable cover or door | $708 | $412 | - | - | - |
$708
-
MMBtu
|
|
TOTAL RECOMMENDED | $76,542 | $66,829 |
$26,817
362,391
kWh
|
$28,320
-
kW-mo/yr
|
$20,697 |
$708
-
MMBtu
|
||
TOTAL IMPLEMENTED | $20,697 | $100 | - | - | $20,697 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs