Assessment Year | 2020 |
---|---|
Principal Product | Rubber Product |
NAICS | 326299: All Other Rubber Product Manufacturing |
SIC | 3061: Molded, Extruded, and Lathe-Cut Mechanical Rubber Goods |
Sales Range | $10 M to 50M |
# of Employees | 192 |
Plant Area |
55,000
ft2
|
Annual Production | 7,000,000
lb
|
Production Hrs. Annual | 7,344
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $266,949 | 5,266,298 |
kWh
|
$0.051 | |
Electricity Demand | $25,058 | 11,112 |
kW-mo/yr
|
$2.26 | |
Electricity Fees | $147,294 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $17,869 | 5,167 |
Tgal
|
$3.46 | |
Water Disposal | $66,958 | 4,633 |
Tgal
|
$14.45 | |
TOTAL YEARLY COSTS | $524,127 | ||||
RECOMMENDED SAVINGS* | $120,095 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $26,744 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,208 | - |
$1,121
22,112
kWh
|
$87
-
kW-mo/yr
|
- | - | - | |
02 | 3.4116: Meter recycled water (to reduce sewer charges) | $75,593 | $7,810 | - | - |
$14,591
-
Tgal
|
$61,002
-
Tgal
|
- | |
03 | 2.2511: Insulate bare equipment | $9,464 | $1,012 |
$8,823
174,025
kWh
|
$641
-
kW-mo/yr
|
- | - | - | |
04 | 2.2511: Insulate bare equipment | $768 | $203 |
$579
11,424
kWh
|
$189
-
kW-mo/yr
|
- | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $9,951 | $5,000 |
$9,277
183,012
kWh
|
$674
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,346 | $1,000 |
$4,850
95,685
kWh
|
$296
-
kW-mo/yr
|
- | - | $(-1,800.0) | |
07 | 2.4226: Use / purchase optimum sized compressor | $792 | $600 |
$785
15,489
kWh
|
$7
-
kW-mo/yr
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,239 | $14,500 |
$10,521
207,556
kWh
|
$765
-
kW-mo/yr
|
- | - | $953 | |
09 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,053 | $1,800 |
$1,053
20,768
kWh
|
- | - | - | - | |
10 | 3.4114: Replace city water with recycled water via cooling tower | $5,681 | $21,000 |
$5,485
108,199
kWh
|
$196
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $120,095 | $52,925 |
$42,494
838,270
kWh
|
$2,855
-
kW-mo/yr
|
$14,591
-
Tgal
|
$61,002
-
Tgal
|
$(-847.0) | ||
TOTAL IMPLEMENTED | $26,744 | $20,500 |
$25,769
508,365
kWh
|
$1,822
-
kW-mo/yr
|
- | - | $(-847.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs