Assessment Year | 2019 |
---|---|
Principal Product | Plasticware |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 280 |
Plant Area |
200,000
ft2
|
Annual Production | 2,400,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,025,570 | 35,315,780 |
kWh
|
$0.029 | |
Electricity Demand | $381,272 | 64,404 |
kW-mo/yr
|
$5.92 | |
Electricity Fees | $389,878 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $36,665 | 5,712 |
Tgal
|
$6.42 | |
TOTAL YEARLY COSTS | $1,833,385 | ||||
RECOMMENDED SAVINGS* | $404,604 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $151,961 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $32,116 | - |
$25,050
826,616
kWh
|
$7,066
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,826 | $1,000 |
$6,962
239,751
kWh
|
$1,944
-
kW-mo/yr
|
- | $(-1,080.0) | |
03 | 2.7241: Install outside air damper / economizer on hvac unit | $78,282 | $44,250 |
$78,282
2,695,658
kWh
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,717 | $4,388 |
$3,785
130,338
kWh
|
$1,057
-
kW-mo/yr
|
$(-125.0) | - | |
05 | 3.4114: Replace city water with recycled water via cooling tower | $107,302 | $83,000 |
$93,845
3,231,565
kWh
|
$13,457
-
kW-mo/yr
|
- | - | |
06 | 2.2622: Replace existing chiller with high efficiency model | $100,517 | $151,300 |
$78,575
2,705,745
kWh
|
$21,942
-
kW-mo/yr
|
- | - | |
07 | 2.2625: Chill water to the highest temperature possible | $73,844 | $147,736 |
$57,724
1,987,754
kWh
|
$16,120
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $404,604 | $431,674 |
$344,223
11,817,427
kWh
|
$61,586
-
kW-mo/yr
|
$(-125.0) | $(-1,080.0) | ||
TOTAL IMPLEMENTED | $151,961 | $88,388 |
$129,642
4,428,270
kWh
|
$23,524
-
kW-mo/yr
|
$(-125.0) | $(-1,080.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs