| Assessment Year | 2019 |
|---|---|
| Principal Product | Auto Parts |
| NAICS | 336310: Motor Vehicle Gasoline Engine and Engine Parts Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | greater than $500 M |
| # of Employees | 800 |
| Plant Area |
417,000
ft2
|
| Annual Production | 4,400,000
units
|
| Production Hrs. Annual | 6,600
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,591,942 | 24,047,466 |
kWh
|
$0.066 |
| Electricity Demand | $18,897 | 51,072 |
kW-mo/yr
|
$0.37 |
| Electricity Fees | $118,340 | - |
|
- |
| Natural Gas | $69,307 | 17,391 |
MMBtu
|
$3.99 |
| TOTAL YEARLY COSTS | $1,798,485 | |||
| RECOMMENDED SAVINGS* | $138,148 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $33,605 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.6212: Turn off equipment during breaks, reduce operating time | $12,280 | - |
$12,280
185,493
kWh
|
- | - | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,606 | - |
$4,560
68,877
kWh
|
$46
-
kW-mo/yr
|
- | - | |
| 03 | 2.2625: Chill water to the highest temperature possible | $1,599 | - |
$1,592
24,056
kWh
|
$7
-
kW-mo/yr
|
- | - | |
| 04 | 2.2515: Use optimum thickness insulation | $2,318 | $290 | - | - |
$2,318
-
MMBtu
|
- | |
| 05 | 2.7224: Reduce space conditioning during non-working hours | $2,102 | - |
$145
2,187
kWh
|
- |
$1,957
-
MMBtu
|
- | |
| 06 | 2.7241: Install outside air damper / economizer on hvac unit | $71,143 | $12,480 |
$71,143
1,074,668
kWh
|
- | - | - | |
| 07 | 2.2437: Recover waste heat from equipment | $24,374 | $48,748 |
$(-721.0)
(-10,892)
kWh
|
$(-5.5)
-
kW-mo/yr
|
$25,100
-
MMBtu
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,801 | $81,000 |
$14,486
218,823
kWh
|
$147
-
kW-mo/yr
|
- | $3,168 | |
| 09 | 2.7135: Install occupancy sensors | $1,925 | $8,061 |
$1,905
28,779
kWh
|
$19
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $138,148 | $150,579 |
$105,390
1,591,991
kWh
|
$214
-
kW-mo/yr
|
$29,375
-
MMBtu
|
$3,168 | ||
| TOTAL IMPLEMENTED | $33,605 | $89,061 |
$30,263
457,151
kWh
|
$173
-
kW-mo/yr
|
- | $3,168 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs