Assessment Year | 2013 |
---|---|
Principal Product | Insulated vinyl windows and patio doors |
NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 309 |
Plant Area |
279,600
ft2
|
Annual Production | 455,177
units
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $294,118 | 5,242,800 |
kWh
|
$0.056 |
Electricity Demand | $208,852 | 12,381 |
kW-mo/yr
|
$16.87 |
Electricity Fees | $1,146 | - |
|
- |
Natural Gas | $36,508 | 3,693 |
MMBtu
|
$9.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $42,618 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,013 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,925 | $4,300 |
$8,006
143,087
kWh
|
$1,919
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,208 | $1,000 |
$4,257
61,700
kWh
|
$551
-
kW-mo/yr
|
- | $(-600.0) | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,013 | - |
$2,704
48,320
kWh
|
$1,309
-
kW-mo/yr
|
- | - | |
04 | 2.2311: Heat treat parts only to required specifications or standards | $10,323 | - |
$6,955
124,301
kWh
|
$3,368
-
kW-mo/yr
|
- | - | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $9,804 | $5,000 |
$13,364
238,857
kWh
|
$6,324
-
kW-mo/yr
|
$(-9,884.0)
-
MMBtu
|
- | |
06 | 2.2511: Insulate bare equipment | $4,345 | $1,205 |
$3,127
52,560
kWh
|
$1,218
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $42,618 | $11,505 |
$38,413
668,825
kWh
|
$14,689
-
kW-mo/yr
|
$(-9,884.0)
-
MMBtu
|
$(-600.0) | ||
TOTAL IMPLEMENTED | $4,013 | - |
$2,704
48,320
kWh
|
$1,309
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs