Assessment Year 2012
Principal Product Airflow Ductwork, AirClean Control Systems, AirSilence Products
NAICS 332322: Sheet Metal Work Manufacturing
SIC 3444: Sheet Metal Work
Sales Range $1
M
to 5
M
# of Employees 83
Plant Area 180,000
ft2
Annual Production 532,689
lb
Production Hrs. Annual 2,500
hrs
Location (State) Ohio

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $83,444 1,766,480
kWh
Electricity Demand $83,444 6,348
kW-mo/yr
Natural Gas $86,752 11,985
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $93,140 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $33,928

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings Administrative Changes Savings
01 2.3131: Reschedule plant operations or reduce load to avoid peaks $23,100 - - $23,100
-
kW-mo/yr
- -
02 3.4116: Meter recycled water (to reduce sewer charges) $7,300 $30,000 - - $7,300
-
Tgal
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $19,664 $91,318 $7,550
146,949
kWh
$12,822
-
kW-mo/yr
- $(-708.0)
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,089 - $389
7,575
kWh
$700
-
kW-mo/yr
- -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,665 $1,000 $1,460
28,410
kWh
$2,625
-
kW-mo/yr
- $(-420.0)
06 2.4239: Eliminate or reduce compressed air usage $3,118 - $1,114
21,686
kWh
$2,004
-
kW-mo/yr
- -
07 2.4239: Eliminate or reduce compressed air usage $1,886 $10,493 $331
6,440
kWh
$595
-
kW-mo/yr
- $960
08 2.7314: Reduce ventilation air $2,956 $6,600 $3,442
37,250
kWh
$1,914
-
kW-mo/yr
- $(-2,400.0)
09 2.9114: Use solar heat to make electricty $30,362 $106,738 $8,280
87,384
kWh
- - $22,082
TOTAL RECOMMENDED $93,140 $246,149 $22,566
335,694
kWh
$43,760
-
kW-mo/yr
$7,300
-
Tgal
$19,514
TOTAL IMPLEMENTED $33,928 $7,600 $6,405
94,921
kWh
$30,343
-
kW-mo/yr
- $(-2,820.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs