Assessment Year | 2010 |
---|---|
Principal Product | sheet metal products |
NAICS | 332313: Plate Work Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $1 M to 5M |
# of Employees | 35 |
Plant Area |
35,000
ft2
|
Annual Production | 39,724
units
|
Production Hrs. Annual | 4,769
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $31,194 | 282,360 |
kWh
|
$0.11 |
Natural Gas | $22,849 | 2,169 |
MMBtu
|
$10.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,980 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,713 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,258 | - | - |
$2,258
-
kW-mo/yr
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $103 | - |
$68
1,090
kWh
|
$35
-
kW-mo/yr
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $243 | $507 |
$163
2,623
kWh
|
$80
-
kW-mo/yr
|
- | |
04 | 2.7144: Install spectral reflectors / delamp | $423 | $200 |
$284
4,577
kWh
|
$139
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,129 | $2,452 |
$2,772
47,678
kWh
|
$1,357
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $660 | $763 |
$443
7,152
kWh
|
$217
-
kW-mo/yr
|
- | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $344 | $1,572 |
$344
5,555
kWh
|
- | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $88 | - |
$59
951
kWh
|
$29
-
kW-mo/yr
|
- | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $21 | - |
$14
227
kWh
|
$7
-
kW-mo/yr
|
- | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $238 | - |
$238
3,840
kWh
|
- | - | |
11 | 2.7224: Reduce space conditioning during non-working hours | $4,159 | $1,678 | - | - |
$4,159
-
MMBtu
|
|
12 | 2.7444: Close holes and openings in building such as broken windows | $190 | $300 | - | - |
$190
-
MMBtu
|
|
13 | 2.7495: Install replacement doors | $6,124 | $50,000 | - | - |
$6,124
-
MMBtu
|
|
TOTAL RECOMMENDED | $18,980 | $57,472 |
$4,385
73,693
kWh
|
$4,122
-
kW-mo/yr
|
$10,473
-
MMBtu
|
||
TOTAL IMPLEMENTED | $2,713 | $507 |
$304
4,891
kWh
|
$2,409
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs