| Assessment Year | 2009 |
|---|---|
| Principal Product | Industrial Process Controls |
| NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
| SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
| Sales Range | $50 M to 100M |
| # of Employees | 170 |
| Plant Area |
80,000
ft2
|
| Annual Production | 17,000
pieces
|
| Production Hrs. Annual | 3,025
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $100,799 | 1,234,364 |
kWh
|
$0.082 |
| Electricity Demand | $14,884 | 274 |
kW-mo/yr
|
$54.32 |
| Electricity Fees | $181 | - |
|
- |
| Natural Gas | $19,662 | 1,692 |
MMBtu
|
$11.62 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $47,959 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $44,625 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $17,000 | $4,900 | - | - | - | $17,000 | |
| 02 | 2.7224: Reduce space conditioning during non-working hours | $9,992 | $1,525 |
$3,293
45,739
kWh
|
- |
$6,699
-
MMBtu
|
- | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $9,237 | - |
$5,050
70,136
kWh
|
- |
$4,187
-
MMBtu
|
- | |
| 04 | 2.6218: Turn off equipment when not in use | $4,088 | - |
$4,088
56,777
kWh
|
- | - | - | |
| 05 | 2.7241: Install outside air damper / economizer on hvac unit | $1,866 | $2,500 |
$1,866
25,912
kWh
|
- | - | - | |
| 06 | 2.2437: Recover waste heat from equipment | $1,734 | $500 |
$252
3,504
kWh
|
$18
-
kW-mo/yr
|
$1,464
-
MMBtu
|
- | |
| 07 | 2.7425: Clean or color roof to reduce solar load | $1,104 | $10,500 |
$1,104
15,336
kWh
|
- | - | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $935 | $2,115 |
$743
10,315
kWh
|
$155
-
kW-mo/yr
|
- | $37 | |
| 09 | 2.6218: Turn off equipment when not in use | $788 | - |
$788
10,950
kWh
|
- | - | - | |
| 10 | 2.1123: Install automatic stack damper | $418 | $400 | - | - |
$418
-
MMBtu
|
- | |
| 11 | 2.7141: Lower light fixtures in high ceiling areas | $364 | $250 |
$267
3,720
kWh
|
$56
-
kW-mo/yr
|
- | $41 | |
| 12 | 2.4231: Reduce the pressure of compressed air to the minimum required | $284 | - |
$19
3,679
kWh
|
$265
-
kW-mo/yr
|
- | - | |
| 13 | 2.6218: Turn off equipment when not in use | $149 | - |
$149
2,076
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $47,959 | $22,690 |
$17,619
248,144
kWh
|
$494
-
kW-mo/yr
|
$12,768
-
MMBtu
|
$17,078 | ||
| TOTAL IMPLEMENTED | $44,625 | $9,440 |
$14,382
203,176
kWh
|
$438
-
kW-mo/yr
|
$12,768
-
MMBtu
|
$17,037 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs