| Assessment Year | 2007 |
|---|---|
| Principal Product | Heavy Capacity Scales |
| NAICS | 333997: Scale and Balance Manufacturing |
| SIC | 3596: Scales and Balances, Except Laboratory |
| Sales Range | less than $500 k |
| # of Employees | 135 |
| Plant Area |
101,000
ft2
|
| Annual Production | 3,000
pieces
|
| Production Hrs. Annual | 5,000
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $231,805 | 3,321,600 |
kWh
|
$0.070 |
| Electricity Demand | $127,454 | 764 |
kW-mo/yr
|
$166.82 |
| Electricity Fees | $10,402 | - |
|
- |
| Natural Gas | $143,447 | 9,268 |
MMBtu
|
$15.48 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $90,779 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $35,735 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7314: Reduce ventilation air | $24,896 | - | - | - | - |
$24,896
-
MMBtu
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,028 | $36,900 |
$5,821
207,900
kWh
|
$7,449
-
kW-mo/yr
|
- | - | $(-242.0) | |
| 03 | 2.3137: Use power during off-peak periods | $12,438 | - | - |
$12,438
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.3511: Use plant owned transformers or lease transformers | $10,225 | $15,000 | - | - | $10,225 | - | - | |
| 05 | 2.2212: Use minimum safe oven ventilation | $9,717 | $595 | - | - | - |
$9,717
-
MMBtu
|
- | |
| 06 | 2.2437: Recover waste heat from equipment | $7,786 | - | - | - | - |
$7,786
-
MMBtu
|
- | |
| 07 | 2.6218: Turn off equipment when not in use | $5,657 | - |
$797
28,125
kWh
|
- | - |
$4,860
-
MMBtu
|
- | |
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,876 | $2,500 |
$2,072
74,000
kWh
|
$1,804
-
kW-mo/yr
|
- | - | - | |
| 09 | 2.3212: Optimize plant power factor | $992 | $3,000 | - | - | $992 | - | - | |
| 10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $876 | $144 |
$245
8,750
kWh
|
$631
-
kW-mo/yr
|
- | - | - | |
| 11 | 2.4239: Eliminate or reduce compressed air usage | $538 | - |
$538
19,200
kWh
|
- | - | - | - | |
| 12 | 2.6218: Turn off equipment when not in use | $430 | - |
$430
15,300
kWh
|
- | - | - | - | |
| 13 | 2.4239: Eliminate or reduce compressed air usage | $320 | $200 |
$140
5,000
kWh
|
$180
-
kW-mo/yr
|
- | - | - | |
| TOTAL RECOMMENDED | $90,779 | $58,339 |
$10,043
358,275
kWh
|
$22,502
-
kW-mo/yr
|
$11,217 |
$47,259
-
MMBtu
|
$(-242.0) | ||
| TOTAL IMPLEMENTED | $35,735 | $2,644 |
$3,544
126,175
kWh
|
$2,435
-
kW-mo/yr
|
- |
$29,756
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs