| Assessment Year | 2001 |
|---|---|
| Principal Product | Metal working, industrial machines and equipment |
| NAICS |
n/a
|
| SIC | 3549: Metalworking Machinery, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 215 |
| Plant Area |
160,000
ft2
|
| Annual Production | 8,750,000
lb
|
| Production Hrs. Annual | 5,000
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $98,121 | 3,368,200 |
kWh
|
$0.029 |
| Electricity Demand | $61,480 | 7,812 |
kW-mo/yr
|
$7.87 |
| Natural Gas | $81,061 | 10,666 |
MMBtu
|
$7.60 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $35,596 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $16,141 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 4.111: Add equipment/ operators to reduce production bottleneck | $12,500 | $2,500 | - | - | - | - | - | - | - | $12,500 | |
| 02 | 3.5112: Reprocess spent oils on site for re-use | $9,526 | $3,323 | - | - | - | - |
$9,526
-
gal
|
- | - | - | |
| 03 | 3.5146: Utilize a central coolant system for cleaning and reuse of metal working fluid | $5,610 | $3,200 | - | - | - |
$3,690
-
gal
|
- | $1,920 | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,574 | $6,830 |
$2,538
54,000
kWh
|
$1,036
-
kW-mo/yr
|
- | - | - | - | - | - | |
| 05 | 3.4114: Replace city water with recycled water via cooling tower | $2,978 | $9,800 |
$(-544.0)
(-19,501)
kWh
|
$(-180.0)
-
kW-mo/yr
|
$4,202
-
Tgal
|
- | - | - | $(-500.0) | - | |
| 06 | 2.7145: Install skylights | $1,341 | $4,455 |
$711
25,476
kWh
|
$630
-
kW-mo/yr
|
- | - | - | - | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $67 | $170 |
$25
900
kWh
|
$42
-
kW-mo/yr
|
- | - | - | - | - | - | |
| TOTAL RECOMMENDED | $35,596 | $30,278 |
$2,730
60,875
kWh
|
$1,528
-
kW-mo/yr
|
$4,202
-
Tgal
|
$3,690
-
gal
|
$9,526
-
gal
|
$1,920 | $(-500.0) | $12,500 | ||
| TOTAL IMPLEMENTED | $16,141 | $9,500 |
$2,563
54,900
kWh
|
$1,078
-
kW-mo/yr
|
- | - | - | - | - | $12,500 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs