Assessment Year | 2000 |
---|---|
Principal Product | aluminum die castings |
NAICS |
n/a
|
SIC | 3363: Aluminum Die-Castings |
Sales Range | $50 M to 100M |
# of Employees | 318 |
Plant Area |
186,000
ft2
|
Annual Production | 22,800,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $439,066 | 18,961,899 |
kWh
|
$0.023 |
Electricity Demand | $509,438 | 36,756 |
kW-mo/yr
|
$13.86 |
Natural Gas | $449,183 | 117,763 |
MMBtu
|
$3.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $114,703 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $57,957 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $40,793 | $76,500 | - | - |
$40,793
-
MMBtu
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $28,367 | $32,550 |
$14,708
700,762
kWh
|
$13,659
-
kW-mo/yr
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $23,347 | $100 |
$11,907
567,116
kWh
|
$11,440
-
kW-mo/yr
|
- | - | - | |
04 | 3.4116: Meter recycled water (to reduce sewer charges) | $12,563 | - | - | - | - | - | $12,563 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,729 | $16,995 |
$2,453
116,940
kWh
|
$3,276
-
kW-mo/yr
|
- | - | - | |
06 | 2.7145: Install skylights | $3,390 | $13,560 |
$1,257
59,789
kWh
|
$2,133
-
kW-mo/yr
|
- | - | - | |
07 | 2.7134: Use photocell controls | $514 | $120 |
$101
4,689
kWh
|
$185
-
kW-mo/yr
|
- | $228 | - | |
TOTAL RECOMMENDED | $114,703 | $139,825 |
$30,426
1,449,296
kWh
|
$30,693
-
kW-mo/yr
|
$40,793
-
MMBtu
|
$228 | $12,563 | ||
TOTAL IMPLEMENTED | $57,957 | $49,765 |
$29,169
1,389,507
kWh
|
$28,560
-
kW-mo/yr
|
- | $228 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs