| Assessment Year | 1997 |
|---|---|
| Principal Product | sheet metal work, stampings |
| NAICS |
n/a
|
| SIC | 3444: Sheet Metal Work |
| Sales Range | $10 M to 50M |
| # of Employees | 120 |
| Plant Area |
69,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 7,000
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $42,964 | 2,027,257 |
kWh
|
$0.021 |
| Electricity Demand | $52,987 | 380 |
kW-mo/yr
|
$139.44 |
| Natural Gas | $110,415 | 20,646 |
MMBtu
|
$5.35 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $31,620 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $20,098 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4226: Use / purchase optimum sized compressor | $5,469 | - |
$2,820
133,060
kWh
|
$2,649
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,083 | $15,018 |
$1,921
90,563
kWh
|
$3,162
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,422 | $637 |
$711
33,411
kWh
|
$711
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $123 | $2,000 |
$62
2,052
kWh
|
$61
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 3.3133: Use other waste concentration methods | $580 | - | - | - | - |
$486
-
gal
|
- | $94 | |
| 06 | 2.1135: Repair furnaces and oven doors so that they seal efficiently | $6,335 | $5,000 | - | - |
$6,335
-
MMBtu
|
- | - | - | |
| 07 | 2.2424: Use heat in flue gases to preheat products or materials | $10,100 | $20,000 | - | - |
$10,100
-
MMBtu
|
- | - | - | |
| 08 | 4.514: Re-arrange equipment layout to reduce handling costs | $2,508 | $4,880 | - | - | - | - | $2,508 | - | |
| TOTAL RECOMMENDED | $31,620 | $47,535 |
$5,514
259,086
kWh
|
$6,583
-
kW-mo/yr
|
$16,435
-
MMBtu
|
$486
-
gal
|
$2,508 | $94 | ||
| TOTAL IMPLEMENTED | $20,098 | $26,898 |
$4,803
225,675
kWh
|
$5,872
-
kW-mo/yr
|
$6,335
-
MMBtu
|
$486
-
gal
|
$2,508 | $94 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs