| Assessment Year | 1996 |
|---|---|
| Principal Product | silicon wafers |
| NAICS |
n/a
|
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 350 |
| Plant Area |
21,000
ft2
|
| Annual Production | 400,000
thousand feet
|
| Production Hrs. Annual | 8,700
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $450,747 | 21,267,878 |
kWh
|
$0.021 |
| Electricity Demand | $497,781 | 34,932 |
kW-mo/yr
|
$14.25 |
| Electricity Fees | $7,200 | - |
|
- |
| Natural Gas | $27,919 | 6,513 |
MMBtu
|
$4.29 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $306,671 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $297,021 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $7,200 | $60,000 | - |
$7,200
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,088 | $2,314 |
$366
15,826
kWh
|
$722
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,041 | $8,081 |
$2,659
125,440
kWh
|
$2,382
-
kW-mo/yr
|
- | - | - | |
| 04 | 3.4111: Use closed cycle process to minimize waste water production | $31,719 | $11,000 | - | - |
$31,719
-
Tgal
|
- | - | |
| 05 | 3.1161: Eliminate/reduce an operation | $9,650 | $5,000 | - | - | - | $9,650 | - | |
| 06 | 3.1161: Eliminate/reduce an operation | $8,523 | - | - | - | - | $8,523 | - | |
| 07 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $101,584 | $40,000 |
$56,098
2,646,249
kWh
|
$45,486
-
kW-mo/yr
|
- | - | - | |
| 08 | 4.631: Install an uninteruptable power supply | $135,600 | $222,868 | - | - | - | - | $135,600 | |
| 09 | 2.4133: Use most efficient type of electric motors | $1,158 | $2,286 |
$601
28,429
kWh
|
$557
-
kW-mo/yr
|
- | - | - | |
| 10 | 3.4115: Recover and reuse cooling water | $5,108 | $5,000 | - | - |
$6,108
-
Tgal
|
$(-1,000.0) | - | |
| TOTAL RECOMMENDED | $306,671 | $356,549 |
$59,724
2,815,944
kWh
|
$56,347
-
kW-mo/yr
|
$37,827
-
Tgal
|
$17,173 | $135,600 | ||
| TOTAL IMPLEMENTED | $297,021 | $351,549 |
$59,724
2,815,944
kWh
|
$56,347
-
kW-mo/yr
|
$37,827
-
Tgal
|
$7,523 | $135,600 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs