Assessment Year | 1996 |
---|---|
Principal Product | pies and cakes |
NAICS |
n/a
|
SIC | 2053: Frozen Bakery Products, Except Bread |
Sales Range | $5 M to 10M |
# of Employees | 70 |
Plant Area |
85,000
ft2
|
Annual Production | 2,000,000
pieces
|
Production Hrs. Annual | 4,500
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $96,240 | 3,008,499 |
kWh
|
$0.032 |
Electricity Demand | $88,788 | 7,331 |
kW-mo/yr
|
$12.11 |
Natural Gas | $43,499 | 9,309 |
MMBtu
|
$4.67 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $12,721 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $4,543 | $3,000 | - |
$4,543
-
kW-mo/yr
|
- | - | - | |
02 | 2.8123: Pay utility bills on time | $879 | - | - | - | - | - | $879 | |
03 | 3.4116: Meter recycled water (to reduce sewer charges) | $1,661 | $300 | - | - | - |
$1,805
-
Tgal
|
$(-144.0) | |
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,886 | $3,500 |
$1,840
87,632
kWh
|
$1,880
-
kW-mo/yr
|
$(-1,834.0)
-
MMBtu
|
- | - | |
05 | 2.8112: Combine utility meters | $311 | $1,000 | - | - | - | - | $311 | |
06 | 2.2122: Install / repair insulation on condensate lines | $251 | $604 | - | - |
$251
-
MMBtu
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,408 | $3,528 |
$338
16,120
kWh
|
$1,070
-
kW-mo/yr
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $336 | $910 |
$119
5,569
kWh
|
$237
-
kW-mo/yr
|
- | - | $(-20.0) | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $474 | $420 |
$133
6,448
kWh
|
$344
-
kW-mo/yr
|
- | - | $(-3.0) | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $972 | - |
$299
14,361
kWh
|
$612
-
kW-mo/yr
|
- | - | $61 | |
TOTAL RECOMMENDED | $12,721 | $13,262 |
$2,729
130,130
kWh
|
$8,686
-
kW-mo/yr
|
$(-1,583.0)
-
MMBtu
|
$1,805
-
Tgal
|
$1,084 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs