Assessment Year 1994
Principal Product flexible packaging for food industry
NAICS
n/a
SIC 2754: Commercial Printing, Gravure
Sales Range $50
M
to 100
M
# of Employees 200
Plant Area 162,000
ft2
Annual Production 0
units
Production Hrs. Annual 7,000
hrs
Location (State) Ohio

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $706,596 12,992,380
kWh
Natural Gas $244,660 83,827
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $65,953 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $39,327

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.1311: Replace electrically-operated equipment with fossil fuel equipment $23,133 $30,000 $35,785
824,150
kWh
$(-12,652.0)
-
MMBtu
02 2.4133: Use most efficient type of electric motors $7,289 $8,288 $7,289
137,163
kWh
-
03 2.7491: Insulate glazing, walls, ceilings, and roofs $14,232 $27,000 - $14,232
-
MMBtu
04 2.7142: Utilize higher efficiency lamps and/or ballasts $2,367 $6,625 $2,367
30,774
kWh
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $6,090 $17,120 $6,090
95,545
kWh
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,413 $1,088 $1,413
21,688
kWh
-
07 2.6218: Turn off equipment when not in use $549 - $549
24,619
kWh
-
08 2.3212: Optimize plant power factor $2,880 $36,000 $2,880
-
kWh
-
09 2.2437: Recover waste heat from equipment $8,000 $40,000 $(-2,935.0)
(-134,525)
kWh
$10,935
-
MMBtu
TOTAL RECOMMENDED $65,953 $166,121 $53,438
999,414
kWh
$12,515
-
MMBtu
TOTAL IMPLEMENTED $39,327 $58,088 $37,747
870,457
kWh
$1,580
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs