| Assessment Year | 1989 |
|---|---|
| Principal Product | CIRCUIT BOARDS |
| NAICS |
n/a
|
| SIC | 3672: Printed Circuit Boards |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
n/a
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 2,250
hrs
|
| Location (State) | Ohio |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $87,418 | 1,337,046 |
kWh
|
$0.065 |
| Fuel Oil #2 | $4,854 | 980 |
MMBtu
|
$4.95 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,278 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,278 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.8114: Change rate schedules or other changes in utility service | $1,105 | $2,000 |
$1,105
-
kWh
|
- | - | |
| 02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,833 | $3,000 |
$7,225
61,254
kWh
|
$(-1,392.0)
-
MMBtu
|
- | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $738 | - |
$696
9,379
kWh
|
- | $42 | |
| 04 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $602 | $400 |
$522
21,395
kWh
|
- | $80 | |
| TOTAL RECOMMENDED | $8,278 | $5,400 |
$9,548
92,028
kWh
|
$(-1,392.0)
-
MMBtu
|
$122 | ||
| TOTAL IMPLEMENTED | $8,278 | $5,400 |
$9,548
92,028
kWh
|
$(-1,392.0)
-
MMBtu
|
$122 | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs