Assessment Year | 2025 |
---|---|
Principal Product | Pressure and temperature process instruments |
NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
Sales Range | $100 M to 500M |
# of Employees | 380 |
Plant Area |
330,000
ft2
|
Annual Production | 1,200,000
units
|
Production Hrs. Annual | 4,300
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $631,545 | 4,604,400 |
kWh
|
$0.14 |
Electricity Demand | $289,870 | 11,290 |
kW-mo/yr
|
$25.68 |
Natural Gas | $83,229 | 11,291 |
MMBtu
|
$7.37 |
TOTAL YEARLY COSTS | $1,004,644 | |||
RECOMMENDED SAVINGS* | $147,162 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,322 | $42,474 |
$17,449
127,219
kWh
|
$873
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,747 | $3,380 |
$10,940
79,804
kWh
|
$2,807
-
kW-mo/yr
|
- | |
03 | 2.9114: Use solar heat to make electricty | $86,822 | $892,123 |
$94,359
687,946
kWh
|
- | $(-7,537.0) | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,573 | $150 |
$6,337
46,201
kWh
|
$236
-
kW-mo/yr
|
- | |
05 | 2.6231: Utilize controls to operate equipment only when needed | $18,450 | $50 |
$18,450
134,514
kWh
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,248 | $2,210 |
$3,248
23,684
kWh
|
- | - | |
TOTAL RECOMMENDED | $147,162 | $940,387 |
$150,783
1,099,368
kWh
|
$3,916
-
kW-mo/yr
|
$(-7,537.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs