| Assessment Year | 2026 |
|---|---|
| Principal Product | Tractor Attachments |
| NAICS | 336360: Motor Vehicle Seating and Interior Trim Manufacturing |
| SIC | 2396: Automotive Trimmings, Apparel Findings, and Related Products |
| Sales Range | $100 M to 500M |
| # of Employees | 166 |
| Plant Area |
195,000
ft2
|
| Annual Production | 1,602,952
units
|
| Production Hrs. Annual | 6,768
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $371,100 | 3,692,500 |
kWh
|
$0.10 |
| Electricity Demand | $72,771 | 12,022 |
kW-mo/yr
|
$6.05 |
| Electricity Fees | $7,964 | - |
|
- |
| Natural Gas | $9,909 | 583 |
MMBtu
|
$17.00 |
| TOTAL YEARLY COSTS | $461,744 | |||
| RECOMMENDED SAVINGS* | $311,405 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,968 | $8,591 |
$2,546
25,330
kWh
|
$261
-
kW-mo/yr
|
$161 | - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,304 | $250 |
$1,088
10,823
kWh
|
$145
-
kW-mo/yr
|
$71 | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $329 | $988 |
$242
2,411
kWh
|
$69
-
kW-mo/yr
|
$18 | - | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,920 | $2,438 |
$1,677
16,687
kWh
|
$139
-
kW-mo/yr
|
$104 | - | |
| 05 | 2.9114: Use solar heat to make electricty | $240,021 | $3,134,000 | - |
$227,013
-
kW-mo/yr
|
$13,008 | - | |
| 06 | 2.7232: Replace existing hvac unit with high efficiency model | $41,479 | $259,458 |
$32,334
321,735
kWh
|
$6,897
-
kW-mo/yr
|
$2,248 | - | |
| 07 | 2.7423: Reduce heat gain by window tinting | $1,938 | $2,695 |
$1,833
18,237
kWh
|
- | $105 | - | |
| 08 | 2.7243: Improve air circulation with destratification fans / other methods | $16,043 | $55,305 |
$15,174
150,981
kWh
|
- | $869 | - | |
| 09 | 2.2437: Recover waste heat from equipment | $5,403 | $8,397 | - | - | - |
$5,403
-
MMBtu
|
|
| TOTAL RECOMMENDED | $311,405 | $3,472,122 |
$54,894
546,204
kWh
|
$234,524
-
kW-mo/yr
|
$16,584 |
$5,403
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs