| Assessment Year | 2024 |
|---|---|
| Principal Product | Hydraulic Cylinders |
| NAICS | 333995: Fluid Power Cylinder and Actuator Manufacturing |
| SIC | 3593: Fluid Power Cylinders and Actuators |
| Sales Range | $10 M to 50M |
| # of Employees | 86 |
| Plant Area |
140,000
ft2
|
| Annual Production | 9,928
units
|
| Production Hrs. Annual | 2,000
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $269,966 | 3,788,039 |
kWh
|
$0.071 | |
| Electricity Demand | $211,394 | 15,244 |
kW-mo/yr
|
$13.87 | |
| Electricity Fees | $17,255 | - |
|
- | |
| Natural Gas | $41,855 | 4,105 |
MMBtu
|
$10.20 | |
| Waste Disposal Costs | |||||
| Water Usage | $12,808 | 3,723 |
Tgal
|
$3.44 | |
| TOTAL YEARLY COSTS | $553,278 | ||||
| RECOMMENDED SAVINGS* | $192,770 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,753 | $500 |
$1,485
20,831
kWh
|
$1,173
-
kW-mo/yr
|
$95 | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,693 | $8,473 |
$5,929
83,151
kWh
|
$3,429
-
kW-mo/yr
|
$335 | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $178,998 | $1,000,734 |
$64,278
901,514
kWh
|
$108,533
-
kW-mo/yr
|
$6,187 | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $531 | $1,463 |
$237
3,318
kWh
|
$276
-
kW-mo/yr
|
$18 | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $688 | $3,738 |
$303
4,256
kWh
|
$361
-
kW-mo/yr
|
$24 | |
| 06 | 2.7135: Install occupancy sensors | $107 | $452 |
$103
1,440
kWh
|
- | $4 | |
| TOTAL RECOMMENDED | $192,770 | $1,015,360 |
$72,335
1,014,510
kWh
|
$113,772
-
kW-mo/yr
|
$6,663 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs