Assessment Year | 2024 |
---|---|
Principal Product | Aircraft Composites |
NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 610 |
Plant Area |
380,000
ft2
|
Annual Production | 2,600
units
|
Production Hrs. Annual | 7,344
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $2,569,804 | 33,399,980 |
kWh
|
$0.077 | |
Electricity Demand | $334,709 | 73,210 |
kW-mo/yr
|
$4.57 | |
Electricity Fees | $31,895 | - |
|
- | |
Natural Gas | $197,542 | 22,343 |
MMBtu
|
$8.84 | |
Waste Disposal Costs | |||||
Water Usage | $53,091 | 17,858 |
Tgal
|
$2.97 | |
Water Disposal | $27,423 | 17,858 |
Tgal
|
$1.54 | |
TOTAL YEARLY COSTS | $3,214,464 | ||||
RECOMMENDED SAVINGS* | $180,210 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $18,036 | $12,615 | - |
$17,840
-
kW-mo/yr
|
$196 | - | - | |
02 | 3.4116: Meter recycled water (to reduce sewer charges) | $14,808 | $5,698 | - | - | - | - |
$14,808
-
Tgal
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,375 | $1,000 |
$3,440
44,739
kWh
|
$887
-
kW-mo/yr
|
$48 | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,484 | $8,591 |
$7,553
98,217
kWh
|
$839
-
kW-mo/yr
|
$92 | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $56,035 | $68,083 |
$50,519
656,943
kWh
|
$4,906
-
kW-mo/yr
|
$610 | - | - | |
06 | 2.7135: Install occupancy sensors | $6,060 | $1,885 |
$5,994
77,940
kWh
|
- | $66 | - | - | |
07 | 2.1113: Reduce combustion air flow to optimum | $5,437 | $26,750 | - | - | - |
$5,437
-
MMBtu
|
- | |
08 | 2.2414: Use waste heat from hot flue gases to preheat | $21,490 | $49,464 | - | - | - |
$21,490
-
MMBtu
|
- | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $40,483 | $47,040 |
$37,028
481,514
kWh
|
$3,015
-
kW-mo/yr
|
$440 | - | - | |
10 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,002 | $15,154 |
$3,736
48,584
kWh
|
$1,212
-
kW-mo/yr
|
$54 | - | - | |
TOTAL RECOMMENDED | $180,210 | $236,280 |
$108,270
1,407,937
kWh
|
$28,699
-
kW-mo/yr
|
$1,506 |
$26,927
-
MMBtu
|
$14,808
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs